Overfilled boxes make splices hard, damage insulation and overheat. The U.S. National Electrical Code assigns each item a volume allowance based on conductor size: every insulated conductor entering the box counts once, all internal cable clamps together count once, each switch or receptacle yoke counts twice and all equipment grounding conductors together count once.
How to use the Box Fill Calculator
- 18 AWG conductors
- 16 AWG conductors
- 14 AWG conductors
- 12 AWG conductors
- 10 AWG conductors
- 8 AWG conductors
- 6 AWG conductors
- Internal cable clamps
- Fittings (luminaire studs, hickeys)
- Devices (switches, receptacles)
- Equipment grounding conductors
- Your box volume (optional)
Results update as you type, and every field accepts the units shown in its menu.
How it works
Enter the number of conductors of each gauge, whether the box has internal clamps, the number of fittings and devices and grounding conductors, and optionally your box’s marked volume.
Conductor volume allowances (NEC Table 314.16(B))
| AWG | in³ per conductor | cm³ |
|---|---|---|
| 18 | 1.50 | 24.6 |
| 16 | 1.75 | 28.7 |
| 14 | 2.00 | 32.8 |
| 12 | 2.25 | 36.9 |
| 10 | 2.50 | 41.0 |
| 8 | 3.00 | 49.2 |
| 6 | 5.00 | 81.9 |
Inputs explained
| Field | What to enter |
|---|---|
| 18 AWG conductors | A number |
| 16 AWG conductors | A number |
| 14 AWG conductors | A number |
| 12 AWG conductors | A number |
| 10 AWG conductors | A number |
| 8 AWG conductors | A number |
| 6 AWG conductors | A number |
| Internal cable clamps | Choose one: No, Yes |
| Fittings (luminaire studs, hickeys) | A number |
| Devices (switches, receptacles) | A number |
| Equipment grounding conductors | A number |
| Your box volume (optional) | Units: in³, cm³ |
Formula
Volume = Σ conductors × allowance for their AWG size
+ 1 allowance (largest) for all clamps, + 1 per fitting, + 2 per device yoke, + 1 for grounds (¼ each beyond four)
Allowances (in³): 18 AWG 1.50, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00
Worked example
Inputs: 18 AWG conductors: 0; 16 AWG conductors: 0; 14 AWG conductors: 4; 12 AWG conductors: 0; 10 AWG conductors: 0; 8 AWG conductors: 0; 6 AWG conductors: 0; Internal cable clamps: Yes; Fittings (luminaire studs, hickeys): 0; Devices (switches, receptacles): 1; Equipment grounding conductors: 2; Your box volume (optional): 18 in³.
Results: Required box volume = 16 in³; Fill of your box = 89 %.
Frequently asked questions
How do I calculate box fill?
Add the NEC 314.16(B) allowances: each conductor by gauge, one for all clamps, two per device, one per fitting and one for all grounds.
Do pigtails count toward box fill?
No. Conductors that start and end inside the box (pigtails) are not counted.
Does a 14 AWG ground count?
All equipment grounding conductors together count as one allowance of the largest one; under NEC 2020, add ¼ allowance for each beyond four.