Box Fill Calculator

Quick answer

The box fill calculator applies NEC 314.16 to find the minimum electrical box volume in cubic inches for the conductors, clamps, fittings, devices and grounding wires inside, and checks a box you already have.

Required box volume
16
Fill of your box
89 %

Overfilled boxes make splices hard, damage insulation and overheat. The U.S. National Electrical Code assigns each item a volume allowance based on conductor size: every insulated conductor entering the box counts once, all internal cable clamps together count once, each switch or receptacle yoke counts twice and all equipment grounding conductors together count once.

How to use the Box Fill Calculator

  1. 18 AWG conductors
  2. 16 AWG conductors
  3. 14 AWG conductors
  4. 12 AWG conductors
  5. 10 AWG conductors
  6. 8 AWG conductors
  7. 6 AWG conductors
  8. Internal cable clamps
  9. Fittings (luminaire studs, hickeys)
  10. Devices (switches, receptacles)
  11. Equipment grounding conductors
  12. Your box volume (optional)

Results update as you type, and every field accepts the units shown in its menu.

How it works

Enter the number of conductors of each gauge, whether the box has internal clamps, the number of fittings and devices and grounding conductors, and optionally your box’s marked volume.

Conductor volume allowances (NEC Table 314.16(B))

AWG in³ per conductor cm³
18 1.50 24.6
16 1.75 28.7
14 2.00 32.8
12 2.25 36.9
10 2.50 41.0
8 3.00 49.2
6 5.00 81.9

Inputs explained

Field What to enter
18 AWG conductors A number
16 AWG conductors A number
14 AWG conductors A number
12 AWG conductors A number
10 AWG conductors A number
8 AWG conductors A number
6 AWG conductors A number
Internal cable clamps Choose one: No, Yes
Fittings (luminaire studs, hickeys) A number
Devices (switches, receptacles) A number
Equipment grounding conductors A number
Your box volume (optional) Units: in³, cm³

Formula

Volume = Σ conductors × allowance for their AWG size + 1 allowance (largest) for all clamps, + 1 per fitting, + 2 per device yoke, + 1 for grounds (¼ each beyond four) Allowances (in³): 18 AWG 1.50, 16 AWG 1.75, 14 AWG 2.00, 12 AWG 2.25, 10 AWG 2.50, 8 AWG 3.00, 6 AWG 5.00

Worked example

Inputs: 18 AWG conductors: 0; 16 AWG conductors: 0; 14 AWG conductors: 4; 12 AWG conductors: 0; 10 AWG conductors: 0; 8 AWG conductors: 0; 6 AWG conductors: 0; Internal cable clamps: Yes; Fittings (luminaire studs, hickeys): 0; Devices (switches, receptacles): 1; Equipment grounding conductors: 2; Your box volume (optional): 18 in³.
Results: Required box volume = 16 in³; Fill of your box = 89 %.

Frequently asked questions

How do I calculate box fill?

Add the NEC 314.16(B) allowances: each conductor by gauge, one for all clamps, two per device, one per fitting and one for all grounds.

Do pigtails count toward box fill?

No. Conductors that start and end inside the box (pigtails) are not counted.

Does a 14 AWG ground count?

All equipment grounding conductors together count as one allowance of the largest one; under NEC 2020, add ¼ allowance for each beyond four.

Sources

  1. NFPA 70 National Electrical Code: Article 314.16