# Generator Power Calculator

URL: https://speedycalculator.com/calculators/physics/generator-power/
Last updated: 2026-11-08

> The generator power calculator finds the apparent power (kVA), real power (kW) and required engine horsepower of a single-phase, three-phase or DC generator from the current, voltage, power factor and efficiency.

## Inputs

- Generator type
- Current (A, mA, µA, kA)
- Voltage (V, kV, mV)
- Power factor
- Generator efficiency (%)

## Results

- Apparent power
- Real power
- Required engine power

## Formula

```
1-phase: S = V·I · 3-phase: S = √3·V·I · DC: P = V·I,  P = S·PF,  engine hp = P/(η·745.7)
```

## Explanation

Generator sizing begins with the load current and voltage. The kVA rating is what the alternator can carry; the kW depends on the load's power factor; and the engine must supply that power plus alternator losses.

### How to use the Generator Power Calculator

- **Generator type**
- **Current**
- **Voltage**
- **Power factor**
- **Generator efficiency (%)**

Results update as you type, every field has its own unit menu, and everything is calculated in your browser.

### How it works

Choose the system, enter the current, voltage, power factor and generator efficiency.

### Inputs explained

FieldWhat to enterGenerator typeChoose one: Single-phase AC, Three-phase AC, DCCurrentUnits: A, mA, µA, kAVoltageUnits: V, kV, mVPower factorA numberGenerator efficiency (%)A number

### Example values

How the main result changes when **Current** changes and everything else stays at the example values above:

Current (A)Real power (kW)2513.856437.520.78465027.712862.534.6417541.569210055.4256

## Worked example

Inputs: Generator type: Three-phase AC; Current: 50 A; Voltage: 400 V; Power factor: 0.8; Generator efficiency (%): 90.

Results: Apparent power = 34.64102 kVA; **Real power = 27.71281 kW**; Required engine power = 41.2928 hp.

## Key terms

- **Alternator**: The electrical part of an AC generator.

## FAQ

**Why rate generators in kVA?**
Their heating depends on current regardless of power factor.

**What power factor do generator ratings assume?**
Usually 0.8.

**Should I oversize a generator?**
Yes, because motor starting currents need extra capacity.

**How do kVA and kW relate?**
kW = kVA × PF.


## Sources

- [OpenStax: University Physics Volume 2](https://openstax.org/details/books/university-physics-volume-2)
- [The Engineering ToolBox](https://www.engineeringtoolbox.com/)