LMTD Calculator (Log Mean Temperature Difference)

Quick answer

The LMTD calculator finds the log mean temperature difference of a parallel-flow or counter-flow heat exchanger from the four terminal temperatures, with an optional correction factor for cross-flow or shell-and-tube designs.

ΔT₁
50 K
ΔT₂
35 K
LMTD
42.0551 K
Corrected LMTD (F·LMTD)
42.0551 K
Heat duty U·A·F·LMTD
42.0551 kW

The temperature difference between two fluids varies along a heat exchanger. The log mean temperature difference is the correct average to use in q = UA·ΔT when sizing exchangers.

How to use the LMTD Calculator

  1. Flow arrangement
  2. Hot inlet
  3. Hot outlet
  4. Cold inlet
  5. Cold outlet
  6. Correction factor F
  7. UA (W/K, optional)

Results update as you type, every field has its own unit menu, and everything is calculated in your browser.

How it works

Choose the flow arrangement and enter the inlet and outlet temperatures of both fluids, the correction factor F (1 for pure counter or parallel flow) and optionally UA.

Inputs explained

Field What to enter
Flow arrangement Choose one: Parallel flow, Counter flow
Hot inlet Units: °C, °F, K
Hot outlet Units: °C, °F, K
Cold inlet Units: °C, °F, K
Cold outlet Units: °C, °F, K
Correction factor F A number
UA (W/K, optional) A number

What each result means

  • Corrected LMTD (F·LMTD) = [Correction factor F]×[LMTD]
  • Heat duty U·A·F·LMTD = [UA (W÷K, optional)]×[Correction factor F]×[LMTD]÷1000

Example values

How the main result changes when Hot inlet changes and everything else stays at the example values above:

Hot inlet (°C) LMTD (K)
45 15.417
67.5 31.0994
90 42.0551
112.5 51.4941
135 60.0884
180 75.7415

Formula

Counter: ΔT₁ = T_h,in − T_c,out, ΔT₂ = T_h,out − T_c,in · Parallel: ΔT₁ = T_h,in − T_c,in, ΔT₂ = T_h,out − T_c,out LMTD = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂), q = U·A·F·LMTD

Worked example

Inputs — Flow arrangement: Counter flow; Hot inlet: 90 °C; Hot outlet: 50 °C; Cold inlet: 15 °C; Cold outlet: 40 °C; Correction factor F: 1; UA (W/K, optional): 1,000.
Results — ΔT₁ = 50 K; ΔT₂ = 35 K; LMTD = 42.0551 K; Corrected LMTD (F·LMTD) = 42.0551 K; Heat duty U·A·F·LMTD = 42.0551 kW.

Key terms

LMTD
Log mean temperature difference.

Frequently asked questions

Why use a logarithmic mean?

The temperature difference decays exponentially along the exchanger.

Why is counter-flow better?

It keeps a more uniform temperature difference and allows temperature cross.

What if ΔT₁ = ΔT₂?

The LMTD equals that common value.

What is the F factor?

A correction for multi-pass and cross-flow exchangers.

Sources

  1. Incropera – Fundamentals of Heat and Mass Transfer (reference text)
  2. The Engineering ToolBox