# Transformer Sizing Calculator

URL: https://speedycalculator.com/calculators/physics/transformer-sizing/
Last updated: 2026-11-08

> The transformer sizing calculator finds the kVA a single-phase or three-phase transformer must supply from the load voltage and current, and suggests the next standard transformer size with a chosen growth margin.

## Inputs

- Phase
- Load voltage (V, kV, mV)
- Load current (A, mA, µA, kA)
- Growth margin (%)

## Results

- Load apparent power
- With margin
- Next standard transformer size

## Formula

```
1-phase: kVA = V·I/1000 · 3-phase: kVA = √3·V·I/1000,  size ≥ kVA × (1 + margin)
```

## Explanation

Transformers are rated in kVA. Choosing one too small makes it overheat; too large wastes money and adds no-load losses. Many designers add 20–25% for future growth.

### How to use the Transformer Sizing Calculator

- **Phase**
- **Load voltage**
- **Load current**
- **Growth margin (%)**

Results update as you type, every field has its own unit menu, and everything is calculated in your browser.

### How it works

Choose the phase, enter the load voltage, load current and a growth margin.

### Inputs explained

FieldWhat to enterPhaseChoose one: Single-phase, Three-phaseLoad voltageUnits: V, kV, mVLoad currentUnits: A, mA, µA, kAGrowth margin (%)A number

### Example values

How the main result changes when **Load voltage** changes and everything else stays at the example values above:

Load voltage (V)Next standard transformer size (kVA)2005030075400100500112.5600150800225

## Worked example

Inputs: Phase: Three-phase; Load voltage: 400 V; Load current: 100 A; Growth margin (%): 25.

Results: Load apparent power = 69.28203 kVA; With margin = 86.60254 kVA; **Next standard transformer size = 100 kVA**.

## Key terms

- **kVA rating**: Apparent power a transformer can continuously supply.

## FAQ

**Why are transformers rated in kVA?**
Their losses depend on current and voltage, not the load's power factor.

**Should I add a margin?**
20–25% is common for future loads.

**What about motor starting?**
Large motors may require a bigger transformer to limit voltage dip.

**Are standard sizes the same everywhere?**
Similar ladders are used; check local suppliers.