# Wire Gauge Calculator (AWG and SWG)

URL: https://speedycalculator.com/calculators/physics/wire-gauge/
Last updated: 2026-11-08

> The wire gauge calculator converts an AWG or SWG gauge number into wire diameter and cross-section area, and finds the resistance per length for the chosen conductor.

## Inputs

- Gauge system
- Gauge number
- Material
- Custom resistivity (Ω·m)

## Results

- Diameter
- Cross-section area
- Area in kcmil
- Resistance per metre
- Resistance per 1,000 ft

## Formula

```
AWG: d = 0.127 mm × 92^((36 − n)/39) · SWG: from the British Standard table · R = ρ/A per metre
```

## Explanation

Wire sizes are often given as gauge numbers where bigger numbers mean thinner wire. AWG is used in North America for electrical wire; SWG survives in the UK for jewellery and sheet metal.

### How to use the Wire Gauge Calculator

- **Gauge system**
- **Gauge number**
- **Material**
- **Custom resistivity**

Results update as you type, every field has its own unit menu, and everything is calculated in your browser.

### How it works

Choose the gauge system and number (AWG 0 = 1/0, −1 = 2/0, −2 = 3/0, −3 = 4/0), and the conductor material.

### Inputs explained

FieldWhat to enterGauge systemChoose one: AWG, SWGGauge numberA numberMaterialChoose one: Copper, Annealed copper, Aluminium, Silver …Custom resistivityUnits: Ω·m

### What each result means

- **Diameter** = [Diameter]
- **Cross-section area** = pi×[Diameter]^2÷4
- **Area in kcmil** = pi×[Diameter]^2÷4÷5.067075e-7

### Example values

How the main result changes when **Gauge number** changes and everything else stays at the example values above:

Gauge numberDiameter (mm)64.115492.9064122.0525151.4495181.0237240.5106

## Worked example

Inputs: Gauge system: AWG; Gauge number: 12; Material: Copper.

Results: **Diameter = 2.05253 mm**; Cross-section area = 3.30877 mm²; Area in kcmil = 6.5299 kcmil; Resistance per metre = 5.07741 mΩ/m; Resistance per 1,000 ft = 1.54759 Ω/kft.

## Key terms

- **AWG**: American Wire Gauge.

## FAQ

**What is the diameter of 12 AWG?**
2.05 mm (3.31 mm²).

**Why do bigger numbers mean thinner wire?**
The gauge counted drawing steps through dies.

**How does area change every 3 AWG?**
It roughly halves.

**Are AWG and SWG the same?**
No, they differ, especially for thick wire.


## Sources

- [OpenStax: University Physics Volume 2](https://openstax.org/details/books/university-physics-volume-2)
- [The Engineering ToolBox](https://www.engineeringtoolbox.com/)
- [NIST: Fundamental physical constants](https://physics.nist.gov/cuu/Constants/)