Three-Phase Power Calculator

Quick answer

The three-phase power calculator finds the real, apparent and reactive power of a balanced three-phase load from line voltage, line current and power factor, plus the phase voltage and current for star (wye) or delta connections.

Real power P
11.77795 kW
Apparent power S
13.85641 kVA
Reactive power Q
7.29932 kVAR
Phase voltage
230.94011
Phase current
20
Phase angle
31.7883 °

Three-phase power delivers smooth, efficient power for motors and industry. In a star connection each phase sees the line voltage divided by √3; in a delta, each phase carries the line current divided by √3.

How to use the Three-Phase Power Calculator

  1. Connection
  2. Line voltage V_L
  3. Line current I_L
  4. Power factor

Results update as you type, every field has its own unit menu, and everything is calculated in your browser.

How it works

Choose the connection, enter the line voltage, line current and power factor.

Inputs explained

Field What to enter
Connection Choose one: Star (wye), Delta
Line voltage V_L Units: V, kV, mV
Line current I_L Units: A, mA, µA, kA
Power factor A number

What each result means

  • Real power P = sqrt(3)×[Line voltage V_L]×[Line current I_L]×[Power factor]÷1000
  • Apparent power S = sqrt(3)×[Line voltage V_L]×[Line current I_L]÷1000
  • Reactive power Q = [Apparent power S]×sqrt(1 – [Power factor]^2)
  • Phase angle = deg(acos([Power factor]))

Example values

How the main result changes when Line voltage V_L changes and everything else stays at the example values above:

Line voltage V_L (V) Real power P (kW)
200 5.889
300 8.8335
400 11.7779
500 14.7224
600 17.6669
800 23.5559

Formula

P = √3·V_L·I_L·PF, S = √3·V_L·I_L, Q = √(S² − P²) · Star: V_ph = V_L/√3, I_ph = I_L · Delta: V_ph = V_L, I_ph = I_L/√3

Worked example

Inputs — Connection: Star (wye); Line voltage V_L: 400 V; Line current I_L: 20 A; Power factor: 0.85.
Results — Real power P = 11.77795 kW; Apparent power S = 13.85641 kVA; Reactive power Q = 7.29932 kVAR; Phase voltage = 230.94011 V; Phase current = 20 A; Phase angle = 31.7883 °.

Key terms

Line voltage
Voltage between two phase conductors.

Frequently asked questions

Why √3?

Line voltages are 120° apart, so V_L = √3·V_ph in star.

Is total power the same in star and delta?

Yes, for the same line voltage and current.

What is a balanced load?

Equal impedance on all three phases.

Why is three-phase used for motors?

It creates a rotating field and smooth torque.

Sources