Generator sizing begins with the load current and voltage. The kVA rating is what the alternator can carry; the kW depends on the load’s power factor; and the engine must supply that power plus alternator losses.
How to use the Generator Power Calculator
- Generator type
- Current
- Voltage
- Power factor
- Generator efficiency (%)
Results update as you type, every field has its own unit menu, and everything is calculated in your browser.
How it works
Choose the system, enter the current, voltage, power factor and generator efficiency.
Inputs explained
| Field | What to enter |
|---|---|
| Generator type | Choose one: Single-phase AC, Three-phase AC, DC |
| Current | Units: A, mA, µA, kA |
| Voltage | Units: V, kV, mV |
| Power factor | A number |
| Generator efficiency (%) | A number |
Example values
How the main result changes when Current changes and everything else stays at the example values above:
| Current (A) | Real power (kW) |
|---|---|
| 25 | 13.8564 |
| 37.5 | 20.7846 |
| 50 | 27.7128 |
| 62.5 | 34.641 |
| 75 | 41.5692 |
| 100 | 55.4256 |
Formula
1-phase: S = V·I · 3-phase: S = √3·V·I · DC: P = V·I, P = S·PF, engine hp = P/(η·745.7)
Worked example
Inputs: Generator type: Three-phase AC; Current: 50 A; Voltage: 400 V; Power factor: 0.8; Generator efficiency (%): 90.
Results: Apparent power = 34.64102 kVA; Real power = 27.71281 kW; Required engine power = 41.2928 hp.
Key terms
- Alternator
- The electrical part of an AC generator.
Frequently asked questions
Why rate generators in kVA?
Their heating depends on current regardless of power factor.
What power factor do generator ratings assume?
Usually 0.8.
Should I oversize a generator?
Yes, because motor starting currents need extra capacity.
How do kVA and kW relate?
kW = kVA × PF.