Breaker Size Calculator

Quick answer

The breaker size calculator adds up up to five appliance loads, finds the load current for a single-phase, three-phase or DC circuit and suggests a breaker rated at 125% of the continuous load, rounded up to a standard size.

Total load
3,100 W
Load current
12.9167
Minimum breaker rating (125%)
16.146 A
Standard breaker size
20 A

Circuit breakers protect wiring from overheating. For continuous loads the US National Electrical Code requires a breaker of at least 125% of the load current. This calculator sums your appliances and finds the next standard breaker size.

How to use the Breaker Size Calculator

  1. Current type
  2. Voltage
  3. Appliance 1 power
  4. Quantity
  5. Appliance 2 power
  6. Quantity
  7. Appliance 3 power
  8. Quantity
  9. Appliance 4 power
  10. Quantity
  11. Appliance 5 power
  12. Quantity

This is an estimate for planning. Electrical installations must comply with local codes and be checked by a qualified electrician. Everything is calculated in your browser.

How it works

Choose the current type and voltage, then enter each appliance’s power and how many there are. Always have an electrician confirm the design and cable size.

Inputs explained

Field What to enter
Current type Choose one: Single-phase AC, Three-phase AC, DC
Voltage Units: V, kV, mV
Appliance 1 power Units: W, kW, mW, hp
Quantity A number
Appliance 2 power Units: W, kW, mW, hp
Quantity A number
Appliance 3 power Units: W, kW, mW, hp
Quantity A number
Appliance 4 power Units: W, kW, mW, hp
Quantity A number
Appliance 5 power Units: W, kW, mW, hp
Quantity A number

What each result means

  • Total load = [Appliance 1 power]×[Quantity] + [Appliance 2 power]×[Quantity] + [Appliance 3 power]×[Quantity] + [Appliance 4 power]×[Quantity] + [Appliance 5 power]×[Quantity]
  • Minimum breaker rating (125%) = 1.25×[Load current]

Example values

How the main result changes when Voltage changes and everything else stays at the example values above:

Voltage (V) Standard breaker size (A)
120 35
180 25
240 20
300 15
360 15
480 15

Formula

I = ΣP / V (1-phase, DC) or ΣP / (√3·V) (3-phase), breaker ≥ 1.25 × I

Worked example

Inputs: Current type: Single-phase AC; Voltage: 240 V; Appliance 1 power: 1,500 W; Quantity: 1; Appliance 2 power: 600 W; Quantity: 2; Appliance 3 power: 100 W; Quantity: 4; Appliance 4 power: 0 W; Quantity: 0; Appliance 5 power: 0 W; Quantity: 0.
Results: Total load = 3,100 W; Load current = 12.9167 A; Minimum breaker rating (125%) = 16.146 A; Standard breaker size = 20 A.

Key terms

Continuous load
A load running for 3 hours or more.

Frequently asked questions

Why 125%?

Breakers shouldn't carry more than 80% of their rating continuously.

Does the breaker size decide the wire size?

The wire must be rated for at least the breaker current.

What about motor loads?

Motors need special sizing for their starting current.

Can I do this myself?

Electrical work must follow local codes; consult a licensed electrician.

Sources

  1. The Engineering ToolBox
  2. NFPA 70: National Electrical Code

Cite this calculator

Speedy Calculator. (2026). Breaker Size Calculator. Speedy Calculator. https://speedycalculator.com/calculators/physics/breaker-size/