Circuit breakers protect wiring from overheating. For continuous loads the US National Electrical Code requires a breaker of at least 125% of the load current. This calculator sums your appliances and finds the next standard breaker size.
How to use the Breaker Size Calculator
- Current type
- Voltage
- Appliance 1 power
- Quantity
- Appliance 2 power
- Quantity
- Appliance 3 power
- Quantity
- Appliance 4 power
- Quantity
- Appliance 5 power
- Quantity
This is an estimate for planning. Electrical installations must comply with local codes and be checked by a qualified electrician. Everything is calculated in your browser.
How it works
Choose the current type and voltage, then enter each appliance’s power and how many there are. Always have an electrician confirm the design and cable size.
Inputs explained
| Field | What to enter |
|---|---|
| Current type | Choose one: Single-phase AC, Three-phase AC, DC |
| Voltage | Units: V, kV, mV |
| Appliance 1 power | Units: W, kW, mW, hp |
| Quantity | A number |
| Appliance 2 power | Units: W, kW, mW, hp |
| Quantity | A number |
| Appliance 3 power | Units: W, kW, mW, hp |
| Quantity | A number |
| Appliance 4 power | Units: W, kW, mW, hp |
| Quantity | A number |
| Appliance 5 power | Units: W, kW, mW, hp |
| Quantity | A number |
What each result means
- Total load = [Appliance 1 power]×[Quantity] + [Appliance 2 power]×[Quantity] + [Appliance 3 power]×[Quantity] + [Appliance 4 power]×[Quantity] + [Appliance 5 power]×[Quantity]
- Minimum breaker rating (125%) = 1.25×[Load current]
Example values
How the main result changes when Voltage changes and everything else stays at the example values above:
| Voltage (V) | Standard breaker size (A) |
|---|---|
| 120 | 35 |
| 180 | 25 |
| 240 | 20 |
| 300 | 15 |
| 360 | 15 |
| 480 | 15 |
Formula
I = ΣP / V (1-phase, DC) or ΣP / (√3·V) (3-phase), breaker ≥ 1.25 × I
Worked example
Inputs: Current type: Single-phase AC; Voltage: 240 V; Appliance 1 power: 1,500 W; Quantity: 1; Appliance 2 power: 600 W; Quantity: 2; Appliance 3 power: 100 W; Quantity: 4; Appliance 4 power: 0 W; Quantity: 0; Appliance 5 power: 0 W; Quantity: 0.
Results: Total load = 3,100 W; Load current = 12.9167 A; Minimum breaker rating (125%) = 16.146 A; Standard breaker size = 20 A.
Key terms
- Continuous load
- A load running for 3 hours or more.
Frequently asked questions
Why 125%?
Breakers shouldn't carry more than 80% of their rating continuously.
Does the breaker size decide the wire size?
The wire must be rated for at least the breaker current.
What about motor loads?
Motors need special sizing for their starting current.
Can I do this myself?
Electrical work must follow local codes; consult a licensed electrician.