Wire sizes are often given as gauge numbers where bigger numbers mean thinner wire. AWG is used in North America for electrical wire; SWG survives in the UK for jewellery and sheet metal.
How to use the Wire Gauge Calculator
- Gauge system
- Gauge number
- Material
- Custom resistivity
Results update as you type, every field has its own unit menu, and everything is calculated in your browser.
How it works
Choose the gauge system and number (AWG 0 = 1/0, −1 = 2/0, −2 = 3/0, −3 = 4/0), and the conductor material.
Inputs explained
| Field | What to enter |
|---|---|
| Gauge system | Choose one: AWG, SWG |
| Gauge number | A number |
| Material | Choose one: Copper, Annealed copper, Aluminium, Silver … |
| Custom resistivity | Units: Ω·m |
What each result means
- Diameter = [Diameter]
- Cross-section area = pi×[Diameter]^2÷4
- Area in kcmil = pi×[Diameter]^2÷4÷5.067075e-7
Example values
How the main result changes when Gauge number changes and everything else stays at the example values above:
| Gauge number | Diameter (mm) |
|---|---|
| 6 | 4.1154 |
| 9 | 2.9064 |
| 12 | 2.0525 |
| 15 | 1.4495 |
| 18 | 1.0237 |
| 24 | 0.5106 |
Formula
AWG: d = 0.127 mm × 92^((36 − n)/39) · SWG: from the British Standard table · R = ρ/A per metre
Worked example
Inputs: Gauge system: AWG; Gauge number: 12; Material: Copper.
Results: Diameter = 2.05253 mm; Cross-section area = 3.30877 mm²; Area in kcmil = 6.5299 kcmil; Resistance per metre = 5.07741 mΩ/m; Resistance per 1,000 ft = 1.54759 Ω/kft.
Key terms
- AWG
- American Wire Gauge.
Frequently asked questions
What is the diameter of 12 AWG?
2.05 mm (3.31 mm²).
Why do bigger numbers mean thinner wire?
The gauge counted drawing steps through dies.
How does area change every 3 AWG?
It roughly halves.
Are AWG and SWG the same?
No, they differ, especially for thick wire.