Wire Size Calculator

Quick answer

The wire size calculator finds the minimum conductor cross-section and the nearest suitable AWG size for a circuit, from the voltage, allowed voltage drop, current, one-way length and conductor material.

Minimum cross-section area
1.9942
Minimum diameter
1.5935
Smallest suitable AWG
14
AWG note
Choose this gauge or thicker (lower number)

Long runs need thicker wire to keep voltage drop low. This sizes the wire for voltage drop only – it must also be large enough for the current (ampacity) under your local electrical code.

How to use the Wire Size Calculator

  1. Current type
  2. Conductor
  3. Source voltage
  4. Allowed voltage drop (%)
  5. Current
  6. One-way length

Results update as you type, every field has its own unit menu, and everything is calculated in your browser.

How it works

Choose the system and conductor, enter the voltage, allowed drop, current and one-way length.

Inputs explained

Field What to enter
Current type Choose one: DC / single-phase AC, Three-phase AC
Conductor Choose one: Copper, Aluminium
Source voltage Units: V, kV, mV
Allowed voltage drop (%) A number
Current Units: A, mA, µA, kA
One-way length Units: m, cm, mm, km, in, ft …

What each result means

  • Minimum cross-section area = [Current type]×[Conductor]×[One-way length]×[Current]÷([Source voltage]×[Allowed voltage drop (%)]÷100)
  • Minimum diameter = sqrt(4×[Minimum cross-section area]÷pi)
  • Smallest suitable AWG = floor(36 – 39×ln([Minimum diameter]÷0.000127)÷ln(92))

Example values

How the main result changes when Source voltage changes and everything else stays at the example values above:

Source voltage (V) Minimum cross-section area (mm²)
115 3.9884
172.5 2.6589
230 1.9942
287.5 1.5954
345 1.3295
460 0.9971

Formula

A = 2·ρ·L·I / V_drop (DC, 1-phase) or √3·ρ·L·I / V_drop (3-phase), AWG = 36 − 39·log₉₂(d/0.127 mm)

Worked example

Inputs — Current type: 1; Conductor: Copper; Source voltage: 230 V; Allowed voltage drop (%): 3; Current: 20 A; One-way length: 40 m.
Results — Minimum cross-section area = 1.9942 mm²; Minimum diameter = 1.5935 mm; Smallest suitable AWG = 14; AWG note = Choose this gauge or thicker (lower number).

Key terms

Ampacity
Current a conductor can carry continuously.

Frequently asked questions

Is voltage drop the only factor?

No – the wire must also carry the current safely (ampacity).

What drop is acceptable?

Typically 3% for branch circuits, 5% total.

Why is aluminium thicker?

It has about 64% higher resistivity than copper.

Do I need an electrician?

Yes – wiring must meet local codes.

Sources

  1. The Engineering ToolBox
  2. NFPA 70 – National Electrical Code

Cite this calculator

Speedy Calculator. (2026). Wire Size Calculator. Speedy Calculator. https://speedycalculator.com/calculators/physics/wire-size/