Transformers are rated in kVA. Choosing one too small makes it overheat; too large wastes money and adds no-load losses. Many designers add 20–25% for future growth.
How to use the Transformer Sizing Calculator
- Phase
- Load voltage
- Load current
- Growth margin (%)
Results update as you type, every field has its own unit menu, and everything is calculated in your browser.
How it works
Choose the phase, enter the load voltage, load current and a growth margin.
Inputs explained
| Field | What to enter |
|---|---|
| Phase | Choose one: Single-phase, Three-phase |
| Load voltage | Units: V, kV, mV |
| Load current | Units: A, mA, µA, kA |
| Growth margin (%) | A number |
Example values
How the main result changes when Load voltage changes and everything else stays at the example values above:
| Load voltage (V) | Next standard transformer size (kVA) |
|---|---|
| 200 | 50 |
| 300 | 75 |
| 400 | 100 |
| 500 | 112.5 |
| 600 | 150 |
| 800 | 225 |
Formula
1-phase: kVA = V·I/1000 · 3-phase: kVA = √3·V·I/1000, size ≥ kVA × (1 + margin)
Worked example
Inputs: Phase: Three-phase; Load voltage: 400 V; Load current: 100 A; Growth margin (%): 25.
Results: Load apparent power = 69.28203 kVA; With margin = 86.60254 kVA; Next standard transformer size = 100 kVA.
Key terms
- kVA rating
- Apparent power a transformer can continuously supply.
Frequently asked questions
Why are transformers rated in kVA?
Their losses depend on current and voltage, not the load's power factor.
Should I add a margin?
20–25% is common for future loads.
What about motor starting?
Large motors may require a bigger transformer to limit voltage dip.
Are standard sizes the same everywhere?
Similar ladders are used; check local suppliers.